Operation mode:PRNZ - TC series solar & Utility hybrid charge control power inverter
Application area:Solar power, wind power, mobile office, post and communications, alarm systems, lighting systems, telecommunications, shopping malls, hotels, Banks, restaurants, hospitals, household appliances, etc
PRNZ - TC series solar & Utility hybrid charge control power inverter, converting the solar panels to provide energy to the user can use electricity. From the aspects of structural design, design of the machine is compact, also can adopt wall-mounted installation;From electrical performance, the machine controlled by single chip microcomputer, pure sine wave output to the load power supply;From the reliability, the all-in-one in high temperature and high humidity environment (ambient temperature 40 ℃ to 60 °C, relative humidity 90%) can work normally, and can adaptto bad load, such as water pump, air compressor, etc.
Built-in MPPT controller, can trace solar panels maximum open-circuit voltage, more energy efficient.
In order to meet the needs of different users, all-in-one solar and grid preference can choose.
♦ Reasonable accurate control: single chip microcomputer control system and issue instructions, to provide a reasonable way of power supply to the load. Different load with different ways of power supply, the power of the load can be ensured and reliable, and can also make a all-in-one reasonable use;
♦ Enough power margin: the power of our all-in-one device, such as transistors, transformer and the controller; the selection of specifications were greater than nominal power; so as to improve the reliability of the machine and service life;
♦ High adaptability to various load: whether impedance load (such as incandescent lamp, electric stove wire, etc.), the capacitive load (such as computers, televisions, etc.) or inductive load (such as water pumps, refrigerators, washing machines, air compressor, etc.), we all-in-one machine can be normal power supply;
♦ High reliability of the product itself: all-in-one itself has PV reverse connect protection, output short circuit protection, over temperature protection, overload protection, battery overcharge protection, battery discharge protection, and many other protective measures, and even if the user operation error, wrong load or mains, all-in-one will not damage, just cut off the output, not to continue the power supply. Thus greatly save the maintenance cost;
♦ Adaptability to high temperature and high humidity environment, the machine can be in the national standard of more than 40 ℃, the highest 60 ℃ environment, relative humidity 90% run continuously;
♦ A variety of optional interface: we provide all-in-one digital color display and LCD display in both English and Chinese. Suitable for different groups. All-in-one LCD display, the user operational stronger, can be used to display the inverter of some key parameters Settings, such as the charging current;
♦ Improve the service life of the battery: according to different types of batteries, set up different ways of charging. For each set of batteries, integrative machine can adjust according to the load and battery capacity battery charge and discharge protection point;
♦ The battery reverse connect protection: this function is optional, after the user chooses, even if the error, the battery, inverter and battery will not be damaged;
♦ Smart cooling control: the machine for forced air cooling heat dissipation, but the cooling fan is not often, but through the internal temperature of the test case to control whether the fan rotation. Thus prolongs the service life of the fan, to improve the reliability of the inverter;
♦ LAN and the remote communication: communication function is optional.If users need LAN communications, can choose RS232 or USB interface.Users such as remote communication is required, then need to configure the SNMP card.
Solar power, wind power, mobile office, post and communications, alarm systems, lighting systems, telecommunications, shopping malls, hotels, Banks, restaurants, hospitals, household appliances, etc
Model No. | 10000TC |
Solar | |
Charge controller | 48V 180A |
voltage protection | 58-60V |
Controller voltage drop | <5% |
Battery over voltage protection | 40V±0.5V |
Static loss | <1% |
Max.PV open circuit voltage | 150V |
Suggest Limited Max. PV of Solar Panel | 7000Wp |
Power inverter | |
Rated power | 7000W |
Peak power | 21000W |
DC voltage | DC 48V |
Utility charger | 48V 50A |
Battery over voltage | 64V |
Charge current | 30A - 50A - 80A |
AC Bypass | 160-275V |
Input frequency | 38-65HZ |
Output waveform | Pure sine wave |
Overioad protection | 100%-120% >lmin auto shut; 120%-150% >30s auto shut; above 150% >3s auto shut |
Over voltage point | Higher than 160V or 265V auto switch to battery mode |
Lack voltage point | lower than 80V (for 110V level) or 160V (for 220V level), auto switch to battery mode |
Transfer time | AC to DC SlOms; DC to AC 510ms |
AC efficiency | > 95% |
PF Power factor | 1 |
Nominal voltage | 220V |
Output voltage | ± 10% |
Output frequency | 60Hz/50Hz ± 1% |
System | |
Protection function | Over temperature, overload, short circuit protection |
Environment | |
Temperature | -10℃ 〜40℃ |
Humidity | 0% ~ 95% Non-condensing |
Structure | |
Product size(mm) | 690x610x540 |
Packing size(mm) | 770x710x620 |
Weight (kg) | |
N.W. | 96 |
G.W. | 102.3 |